Extron-electronics MLC 104 SIS Programming and Control Manual de usuario Pagina 32

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 31
SIS
Programming and Control, cont’d
5-32
PRELIMINARY
MLC 104 Series • SIS
Programming and Control
Command/response table for special function SIS commands, continued
Command ASCII Command Response
X?
values
(host to MLC) (MLC to host) and additional descriptions
Miscellaneous settings
Enable switcher slaving
X?
*41 # Slave*
X?
For
X?
,
0 = disable control of a slaved
Extron MLS switcher,
1 = enable (default) MLS slaved
switcher control
Volume knob mode
24
X?
*46 # VolMode*
X?
For
X?
,
0 = discrete volume values
1 = continuous increment/
decrement.
Max. volume
24
X?
*47 # VolMax*
X?
For maximum volume,
X?
is 1 to 100.
40 = stand-alone MLC default,
100 = default for an MLC with a
slaved, detected MLS switcher.
Maximum volume cannot be changed while an MLS switcher is detected at the MLC’s MLS slave switcher port.
When the maximum volume is changed, the volume level and the volume limit during display power-up (11#) are set
to 25% of the new maximum volume setting.
Vista de pagina 31
1 2 ... 27 28 29 30 31 32 33 34 35 36

Comentarios a estos manuales

Sin comentarios